Huayuan Gaoke Cable Co.,Ltd.
Arial Insulated Cable,Stranded Aluminum Conductor Cable,Aluminum Alloy Neutral Supporting Cores Cable
Payment Type: | L/C,T/T,D/P,Western Union |
---|---|
Incoterm: | FOB,CFR,CIF,FCA,CPT,CIP |
Min. Order: | 500 Meter |
Model No.: ABC
Brand: HUAYUAN YONGTONG
Application: Overhead
Voltage: Low and Medium Voltage Cable
Current: AC Cable
Insulation Material: XLPE
Sheath Material: PVC
Material Shape: Round Wire
Certification: ISO
Brand: HUAYUAN YONGTONG
Packaging: Drums
Productivity: 100KM/M
Transportation: Ocean,Land,Air
Place of Origin: BEIJING,CHINA
Supply Ability: 100KM/M
Certificate: CE,CCC,ISO
Port: Tianjin Port,Shanghai Port,Qingdao Port
Payment Type: L/C,T/T,D/P,Western Union
Incoterm: FOB,CFR,CIF,FCA,CPT,CIP
1. SCOPE
This specification covers the general requirements and performance of conductor which Huayuan Gaoke offered including electrical characteristics, mechanical characteristics, packing information etc.
2. REFERENCES
The conductor which Huayuan Gaoke offered shall be designed, manufactured and tested according to international standards as follows:
Quality Control Standard ISO 9001 Quality Management Systems ISO 14001 Environmental Management Systems Standard ASTM B231 Standard Specification for Aluminum conductor ASTM B398 Standard Specification for Aluminum-Alloy 6201-T81 Wire for Electrical Purposes ASTM B230 Standard Specification for Aluminum 1350-H19 Wire for Electrical Purposes ASTM B399 Standard of test method for plain strain fracture toughness of metallic materials ICEA S -76-474 600V aerial bundle cable
3 CONSTRUCTURE AND SPECIFICATIONS FOR CABLE
3.1 Cable structure
3.2 Conductor Technical Structure
Parameter Unit Value 1: Aluminum alloy wire pcs/mm/(In.) 7/3.37(0.1327) 2: Aluminum wire 7/3.12(0.1288) 3.XLPE insulation 1.5/12.4(0.0600/0.4921) 4: outer diameter 28.8(1.026) Stranding direction of outer layer Direction right Insulated conductor diameter mm/(in.) 9.36(0.3864) Neutral conductor diameter mm/(in.) 10.1 (0.3981)
3.3 Component cable Characteristics
Parameter Unit Value Type of cable ABC NO. of core 2+neutral Conductor Size AWG or Kcmil 1/0 Diameter & Deviation of conductor Mm/in. 3.12(+0.03,-0.03)/(0.1288) Calculated cross section mm2 53.5 Weight Pounds/1000FT 397 Tensile strength Mpa 165 (before stranding/after stranding) Condutor Max. temperature with full load current in cable when in air ℃ 90 Continuous current rating under the specified installation and operating conditions. Conductor temperature 90° C , Air temperature 35 ° C A 161 DC Resistivity at 20℃ Ω·mm2/m 0.0283*10-7
4. TEST REQUIREMENTS FOR CABLE
The following test items shall be carried out according to corresponding reference.
No Item Reference Tests of Steel wire 1 Dimensions Insulated conductor 0.3864 ft Neutral conductor 0.3981 ft 2 Construction of Aluminum conductor 7 × 0.1288 ft 3 Construction of Aluminum alloy neutral 7 × 0.1327 ft 3 Lay length of conductor outer layer 3.864 ft ~4.508 ft 3 Tension at 1% elongation ASTM B398, B230 4 Conductor dc resistance at 25 deg 0.551 Ω/1000ft 5 Rated Strength Insulated conductor 8.83 kN Aluminum alloy neutral 19.0 kN Test of insulation 1 Nominal thickness of insulation 54 mils 2 Minimum Thickness of insulation 60 mils 3 Nominal outer diameter 0.4921 ft 4 A spark test AC 8.5 kV 5 Voltage test 3kV / 5 min Test of cable 1 Lay length of insulation and neutral conductor 40 ft ~44 ft 2 Nominal outer diameter 1.026 ft
Advanced Manufacturing Equipments
Advanced Testing Equipments
The company introduced the world's advanced level wire & cable production and testing equipment, such as DV-6E spectrum analyzer, online micro pore impurity tester, etc.
Advanced Testing Equipment Guarantee High Quality Production
Product Categories : Aerial Insulated Cable