http://www.bjhygkcable.com
Home > Products > Middle Voltage Power Cable > 33KV 1*400sqmm Copper Conductor XLPE Insulated Power Cable

33KV 1*400sqmm Copper Conductor XLPE Insulated Power Cable

    Payment Type: L/C,T/T,D/P,Western Union
    Incoterm: FOB,CFR,CIF,FCA,CPT
    Min. Order: 500 Meter
Basic Info

Model No.N2XSY, N2XSEY, NA2XSY, NA2XSEY, N2XSRY, NA2XSRY, N2XSEBY, N2XSEYBY, NA2XSEBY, N2XSERY, NA2XSERY,

BrandHUAYUAN YONGTONG

TypeInsulated

Conductor TypeStranded

ApplicationUnderground

Conductor MaterialCopper

Sheath MaterialPVC

Insulation MaterialXLPE

Material ShapeRound Wire

Range of ApplicationLSOH

CertificationISO9001

BrandHUAYUAN YONGTONG

Additional Info

PackagingDrums

Productivity100km/m

TransportationOcean,Land,Air

Place of OriginBEIJING CHINA

Supply Ability100KM/M

CertificateCE CCC ISO

HS Code8544601200

PortTianjin Port,Shanghai Port,Qingdao Port

Payment TypeL/C,T/T,D/P,Western Union

IncotermFOB,CFR,CIF,FCA,CPT

Product Description

TECHNICLA DATA SHEET FOR 33 kV 1C 400 SQmm POWER CABLE

NO. ITEM  UNIT DATA
1 Name of Manufacturer: Beijing Huayuan Gaoke
Cable Co.,Ltd. 
2 Country of Manufacturer:  China 
3 Which type of manufacturing process viz. Continuous Catanery Vulcanisation (CCV) or vertical Catanery Vulcanisation system (VCV) or horizontal MDCV will be used to ensure circularity and concentricity of the extruded layers around the conductor. VCV
4 Type of Cable: Cu/XLPE/CWS/PVC/STA/PVC
5 Rated nominal voltage kV 19/33
6 Rated Maximum voltage kV 36
7 Nominal cross-sectional area of Conductor Sq.mm 400
8 Conductor
8.1 Material Copper
8.2  Shape & formation circular
8.3  Diameter of conductor  mm 23.8
8.4 Dia.Of Single Wire/Number of strands mm/ 2.98/60
9 Conductor Screen 
9.1 Material Semi conductor tape + semi conductive material
9.2 Thickness of semi-conductor  screen mm 0.12+0.8
9.3 Diameter of Semi-conductor(Approx.) mm 25.8
10 Insulation
10.1 Material XLPE
10.2 Insulation Thickness(Min.Avg.) mm 9.3
10.3 Diameter of Insulation(Approx.) mm 44.5
11 Insulation Screen
11.1 Material Semi-conductive material
11.2 Insulation Screen Thickness mm 0.8
11.3 Diameter of Insulation screen(Approx.) mm 46.1
12 Water Barrier
12.1 Material semi-conducting water swellable tape
12.2 Water barrier thickness((Nominal) mm 0.3
12.3 Diameter of Insulation screen(Approx.) mm 47.4
13  Metallic Screen:
13.1 Material Copper wire+ copper tape 
13.2 Diameter of wire /NO. mm/ 0.8/50
13.3 Thickness of tape/layer mm/ 0.1/1
13.4 Cross section of the Metallic Screen mm2 26
13.5  Diameter of the cable across the metallic screen(Approx.) mm 49
14 Bedding 
14.1  Material non-woven fabrics tape
14.2 Approximate thickness (Nominal) mm 0.2
14.3 Diameter of bedding tape (Approx.) mm 50
15 Inner sheath
15.1 Material PE laminated Aluminum tape.
15.2 Thickness(Nominal) mm 0.2
15.3 Diameter Over the inner sheath (Approx.) mm 51
16 Extrusion Inner sheath
16.1 Material FRLSOH PVC
16.2 Thickness(Nominal) mm 1.6mm
16.3 Diameter  (Approx.) mm 54.2
17 Armouring
17.1 Material Nonmagnetic steel tape
17.2 Thickness /layer  mm/ 0.5/2
17.3 Diameter  (Approx.) mm 56.2
18 Outer Sheath
18.1 Material FRLSOH PVC
18.2 Outer Sheath Thickness(Nominal) 2.9
18.3 Over Diameter(Approx.) 62
19 Conductor Weight kg/km 3542
19.1 Total Cable Weight (Approx.) kg/km 7185
19 Minimum Bending Radius
19.1 During Installation mm 950
19.2 Installed mm 600
20 Maximum Pulling Tension
20.1 Of Conductor kN 28
21  Continuous current rating under the specified installation and operating conditions.    Conductor temperature 90° C    . Ground    temperature 35° C    and    depth    of laying 1500 mm
21.1 In Air Amp 629
21.2 In Ground Amp 465
21.3 In pipeline Amp 438
22 Maximum value of electric stresses at the conductor screen (Calculation to be shown separately)  kV/mm  2.72
22.1 Maximum value of dielectric stress at the insulation  kV/mm  1.57
23 Short circuit capacity of conductor for 1/2/3    second assuming    conductor temperature of 90 ° C prior to short    circuit and 250 ° C during short circuit
23.1 1.0 Secs kA 57.4
23.2 2.0 Secs kA 40.7
23.3 3.0 Secs kA 33.3
24 Short circuit capacity of metallic screen    for    1/2/3 second     at     screen temperature of 80 ° C prior to short circuit    and 200 ° C during short circuit
24.1 1.0 Secs kA 3.4
24.2 2.0 Secs kA 2.4
24.3 3.0 Secs kA 2
25 Screen voltage under maximum operating conditions assuming all circuits connected kV per km 0.05
26 TEST
26.1 Maximum D.C. resistance of conductor  per km. at 20 degree C.  Ohm 0.047
26.2 Maximum A.C. resistance of conductor per km. at 90 degree C.  Ohm 0.0614
26.3  Maximum electrostatic capacitance per km. of cable. μF 0.233
26.4 Partial discharge at 1.50 Uo pc 10
26.5 A.C.  Enduring Test voltage 2.5U0/ hours  kV/mim May-70
26.6 D.C.Out sheath  Enduring Test voltage  kV/mim 5kV/1min
26.7 Impulse test voltage kV 170
27 Approximate drum dimension (dia & width) mm/mm 2200*1400
28 Maximum length of cable in a drum (Metres) m 600
28.1 Minimum length of cable in a drum  (Metres) m 500
29 Approximate gross weight of cable in a drum  TON 4.3
30 Expected Cable life. Year 30


Drawing of Configuration

CU/XLPE/CWS/PVC/STA/PVC 19/33(36) kV 1C 400 mm2


CU/XLPE/CWS/PVC/STA/PVC 19/33(36) kV 1C 400 mm2

Construction

Thickness(mm)

Diameter(mm)

1 --- Copper conductor

 

23.8(+0.2,-0.2)

2 --- Semi conductor tape +conductor screen

0.12+0.8

25.8

3 --- Insulation

9.3

44.5(+0.5,-0.5)

4 --- Insulation screen

0.8

46.1

5 ---Semi-conducting swelling tape

0.3

47.4

6 --- Copper wires +Copper tape

0.8+0.1

49.0

7 ---Inner shearh(bedding tape+ PE laminated Aluminum tape.)

0.2+0.2

51.0

8 --- Extrusion FRLSOH PVC Inner sheath

1.6

54.2

9 --- Double nonmagnetic steel tape armouring

0.5

56.2

10---FRLSOH PVC outer sheath

2.9

62.2(+2.0,-2.0)




Drum

Drum Structure

d1:2200mm 

L1:1400mm

500m per drum

H :2200mm

L :2200mm

W:1400mm

Wight: 200 kg


Advanced Manufacturing Equipments

Product Equipment


 Advanced Testing Equipments  

      The company introduced the world's advanced level wire & cable production and testing equipment, such as DV-6E spectrum analyzer, online micro pore impurity tester, etc. 

        Advanced Testing Equipment     Guarantee High Quality Production

Test Equipment


Foreign Customers in our Factory

 Packages

Packages

  Our Honor

 We got trust and praise from all customers by outstanding quality and good reputation. To  providefirst-rate products and service for society is the pursuit of staffs of  our Company forever. The after-sale service department provides series of before-sale,selling and  after-sale, which solve the worries behind for customers and provide complete and rapid service  for customers. Customers' satisfaction is the best return for staffa of our Company.

Certificates 

1.33k Cable  2.Three Core Copper Conductor   3.Five Core Copper Conductor  4.Copper Wire Screened Cable  5.MV XLPE Cable

Product Categories : Middle Voltage Power Cable

Email to this supplier
  • *Subject:
  • *Messages:
    Your message must be between 20-8000 characters
Communicate with Supplier?Supplier
Crazy Zhang Mr. Crazy Zhang
What can I do for you?
Contact Supplier