Huayuan Gaoke Cable Co.,Ltd.
MV XLPE Insulated Power Cable,Underground Power Cable for Channel,For Industry Plants and Terminal Plants Power Cable
Payment Type: | L/C,T/T,D/P,Western Union |
---|---|
Incoterm: | FOB,CFR,CIF,FCA,CPT |
Min. Order: | 1000 Meter |
Model No.: N2XS(F)2Y
Brand: HUAYUAN YONGTONG
Type: Insulated
Conductor Type: Stranded
Application: Underground
Conductor Material: Copper
Sheath Material: Crosslinking
Insulation Material: XLPE
Material Shape: Round Wire
Range of Application: LSOH
Certification: ISO9001
Brand: HUAYUAN YONGTONG
Packaging: DRUMS
Productivity: 100KM/M
Transportation: Ocean,Land,Air
Place of Origin: BEIJING, CHINA
Supply Ability: 100KM/M
Certificate: CE,ISO,CCC
HS Code: 8544601200
Port: Tianjin Port,Shanghai Port,Qingdao Port
Payment Type: L/C,T/T,D/P,Western Union
Incoterm: FOB,CFR,CIF,FCA,CPT
Medium voltage cable N2XS(F)2Y 1X50/16 under rated voltage 6/10 kV
N2XS(F)2Y
Medium voltage cables with XLPE Insulation
HD 620 10C
DIN VDE 0276-620
Application:
The cables are suitable for installation indoors, outdoors, in the ground and in water. Installation to be carried out in the ground or in a cable channel.
Specification in common use
conductor material: | bare copper |
conductor construction: | stranded, class 2 |
insulation: | XLPE DIX8 |
sheathing material: | polyethylene DMP2 |
longitudinally water-tight: | yes |
colour of outer sheath: | black |
meter mark: | yes |
flame retardant: | no |
UV-resistant: | yes |
maximum temperature | 90℃ |
at conductor: |
|
max. operating | 70℃ |
temperature, fixed: |
|
temperature, moved/during | -20 - +70℃ |
installation: |
|
bending radius, fixed | 15 x DA |
installation: |
|
partial discharge: | 2 pC |
Rated voltage for Medium voltage cable N2XS(F)2Y 1X50/16
| N2XS(F)2Y 6/10 kV | N2XS(F)2Y 12/20 kV | N2XS(F)2Y 18/30 kV |
nominal voltage Uo: | 6 kV | 12 kV | 18 kV |
nominal voltage U: | 10 kV | 20 kV | 30 kV |
maximum permitted operating | 12 kV | 24 kV | 36 kV |
voltage in 3-phase systems: |
|
|
|
test voltage: | 21 kV | 42 kV | 63 kV |
Detailed specification for N2XS(F)2Y 6/10 kV 1X50/16
diameter of conductor | 8.6 |
conductor resistance | 0.387 |
thickness of insulation | 3.4 |
ampacity (in air) | 236 |
ampacity (in ground) | 220 |
short circuit current (1 s) | 7.15 |
bending radius, fixed installation | 375 |
thickness of outer sheath | 2.5 |
outer diameter | 25 |
tensile strength (during installation) | 2500 |
copper | 660 |
weight | 1150 |
1. THE MV XLPE Cable 2.Electrical Cable Wires 3. Underground Cable 4.20kv Cable 5.Building Wire
Product Categories : Middle Voltage Power Cable