Huayuan Gaoke Cable Co.,Ltd.
Aluminum Alloy Conductor Cable,XLPE Insulated Steel Wire Armoured Cable,15KV Power Cable
Unit Price: | USD 2 / Kilometer |
---|---|
Payment Type: | L/C,T/T,D/P,Paypal,Money Gram,Western Union |
Incoterm: | FOB,CFR,CIF,FCA,CPT,CIP |
Min. Order: | 5 Kilometer |
Model No.: YJLHV32 8.7-15KV
Brand: HUYUAN YONGTONG
Application: Construction
Voltage: Low and Medium Voltage Cable
Current: AC Cable
Insulation Material: XLPE
Sheath Material: Crosslinking
Material Shape: Round Wire
Wire Core Material: Bare Copper Wire
Certification: ISO
Model: YJLV22
Brand: HUAYUAN YONGTONG
Packaging: DRUM
Productivity: 200KM/MONTH
Transportation: Ocean,Land,Air
Place of Origin: CHINA
Supply Ability: 200KM/MONTH
Certificate: CE,CCC,ISO
HS Code: 8544601200
Port: Tianjin Port,Shanghai Port,Beijing
Payment Type: L/C,T/T,D/P,Paypal,Money Gram,Western Union
Incoterm: FOB,CFR,CIF,FCA,CPT,CIP
U | Um | Uo | |
First class | Second class | ||
1 | 1.2 | 0.6 | 0.6 |
3 | 3.6 | 1.8 | 3.6 |
6 | 7.2 | 3.6 | 6 |
10 | 12 | 6 | 8.7 |
15 | 17.5 | 8.7 | 12 |
20 | 24 | 12 | 18 |
35 | 42 | 21 | 26 |
Type | No. of cores | Nominal Cross sectional area m2 |
Aluminum alloy conductor | ||
YJLHV32 | 1 | 25-630 |
3 | 25-630 | |
*The armoured single-core cables are used for D.C system only. As for A.C system non-magnetic armoured material should be used. Or magnetic isolation measures should be applied. |
Nominal cross sectional area of conductor(mm²) | Nominal insulation thickness(mm) | 8.7/10KV 8.7/15KV YJLHV32 | |
Approx overall diameter(mm) | Cable weight max(kg/kn) | ||
1×25 | 4.5 | 29.0 | 1587 |
1×35 | 4.5 | 30.0 | 1704 |
1×50 | 4.5 | 31.5 | 1839 |
1×70 | 4.5 | 33.0 | 2002 |
1×95 | 4.5 | 34.9 | 2220 |
1×120 | 4.5 | 37.5 | 2770 |
1×150 | 4.5 | 39.1 | 2907 |
1×185 | 4.5 | 40.8 | 3124 |
1×240 | 4.5 | 43.1 | 3485 |
1×300 | 4.5 | 45.7 | 3877 |
1×400 | 4.5 | 48.9 | 4396 |
1×500 | 4.5 | 52.6 | 5018 |
1x630 | 4.5 | 56.6 | 5746 |
3×25 | 4.5 | 52.4 | 4378 |
3×35 | 4.5 | 55.7 | 4740 |
3×50 | 4.5 | 58.9 | 5222 |
3×70 | 4.5 | 62.6 | 5815 |
3×95 | 4.5 | 66.4 | 6501 |
3×120 | 4.5 | 69.9 | 7068 |
3×150 | 4.5 | 73.7 | 7814 |
3×185 | 4.5 | 77.3 | 8510 |
3×240 | 4.5 | 84.2 | 10650 |
3×300 | 4.5 | 89.5 | 11934 |
3×400 | 4.5 | 96.8 | 13756 |
3x500 | 4.5 | 104.5 | 15836 |
3x630 | 4.5 | 112.6 | 18105 |
Nominal cross-sectional area of conductor(mm²) | Rated Voltage KV |
8.7/10 8.7/15 | |
Capacitance/phase μF/km | |
1x25 | 0.6474 |
1x35 | 0.6248 |
1x50 | 0.6011 |
1x70 | 0.5765 |
1x95 | 0.5608 |
1x120 | 0.5473 |
1x150 | 0.5341 |
1x185 | 0.5252 |
1x240 | 0.5143 |
1x300 | 0.5032 |
1x400 | 0.4927 |
1x500 | 0.4848 |
1x630 | 0.4748 |
3x25 | 0.4061 |
3x35 | 0.3862 |
3x50 | 0.3655 |
3x70 | 0.3445 |
3x95 | 0.3290 |
3x120 | 0.3178 |
3x150 | 0.3071 |
3x185 | 0.3009 |
3x240 | 0.2904 |
3x300 | 0.2817 |
3x400 | 0.2714 |
3x500 | 0.2641 |
3x630 | 0.2596 |
Nominal cross-sectional area of conductor(mm²) | Rated Voltage KV |
8.7/10 8.7/15 | |
Short circuit current | |
1x25 | 1094 |
1x35 | 1092 |
1x50 | 1091 |
1x70 | 1090 |
1x95 | 1086 |
1x120 | 1266 |
1x150 | 1265 |
1x185 | 1264 |
1x240 | 1262 |
1x300 | 1261 |
1x400 | 1256 |
1x500 | 1253 |
1x630 | 1252 |
3x25 | 2958 |
3x35 | 2958 |
3x50 | 2958 |
3x70 | 2958 |
3x95 | 2958 |
3x120 | 3031 |
3x150 | 3031 |
3x185 | 3031 |
3x240 | 3031 |
3x300 | 3031 |
3x400 | 3031 |
3x500 | 3031 |
3x630 | 3031 |
Aluminium Alloy Conductor | Nominal Cross sectional area of conductor mm2 | In the air | In the ground | ||||
Air temperature:40ºC | Air temperature:25ºC | ||||||
Single Core | Three Core | Single Core | Three Core | ||||
| | | | ||||
25 | 110 | 130 | 90 | 115 | 120 | 100 | |
35 | 135 | 155 | 110 | 135 | 145 | 120 | |
50 | 160 | 190 | 130 | 160 | 175 | 140 | |
70 | 20 | 235 | 165 | 200 | 215 | 170 | |
95 | 24 | 290 | 200 | 240 | 255 | 210 | |
120 | 280 | 335 | 225 | 270 | 290 | 235 | |
150 | 32 | 380 | 255 | 305 | 330 | 260 | |
185 | 365 | 435 | 295 | 345 | 370 | 300 | |
240 | 435 | 515 | 345 | 400 | 435 | 345 | |
300 | 500 | 595 | 390 | 455 | 490 | 390 | |
400 | 585 | 695 | 450 | 520 | 565 | 440 | |
500 | 680 | 810 | - | 595 | 650 | - | |
630 | 790 | 950 | - | 680 | 745 | - |
Soil temperature(ºC) | 15 | 20 | 25 | 30 | 35 | 40 | 45 |
Rating factor | 1.09 | 1.04 | 1.0 | 0.96 | 0.92 | 0.87 | 0.83 |
Rating factors for soil Thermal resistivityºC.m/w | 1.0 | 1.2 | 1.5 | 2.0 | 2.5 | 3.0 | 3.5 |
Three cores | 1.0 | 0.943 | 0.877 | 0.792 | 0.736 | 0.675 | 0.641 |
Single core | 1.0 | 0.934 | 0.850 | 0.748 | 0.692 | 0.635 | 0.598 |
Air temperature(ºC) | 20 | 25 | 30 | 35 | 40 | 45 | 50 |
Correction factor | 1.18 | 1.14 | 1.10 | 1.05 | 1.0 | 0.95 | 0.89 |
Product Categories : 3 Core Power Cables