http://www.bjhygkcable.com
Home > Products > Copper Conductor Power Cable > 12KV Copper Conductor XLPE Insulation with PVC Outer Sheath Power Cable and line

12KV Copper Conductor XLPE Insulation with PVC Outer Sheath Power Cable and line

    Payment Type: L/C,T/T,D/P
    Incoterm: FOB,CFR,CIF,FCA,CPT
    Min. Order: 500 Meter
Basic Info

Model No.YJV

BrandHUAYUAN YONGTONG

TypeInsulated

Conductor TypeStranded

ApplicationUnderground

Conductor MaterialCopper

Sheath MaterialPVC

Insulation MaterialXLPE

Material ShapeRound Wire

Range of ApplicationRefractory

CertificationCE

BrandHUAYUAN YONGTONG

Additional Info

PackagingDrums

Productivity100KM/M

TransportationOcean,Land,Air

Place of OriginBEIJING,CHINA

Supply Ability100KM/M

CertificateCE,ISO,CCC

HS Code8544601200

PortTianjin Port,Shanghai Port,Beijing

Payment TypeL/C,T/T,D/P

IncotermFOB,CFR,CIF,FCA,CPT

Product Description

TECHNICLA DATA SHEET FOR 12kV 3C 50 SQmm POWER CABLE

NO. ITEM  UNIT DATA
1 Name of Manufacturer: Beijing Huayuan Gaoke
Cable Co.,Ltd. 
1.2 Country of Manufacturer:  China 
2 Which type of manufacturing process viz. Continuous Catanery Vulcanisation (CCV) or vertical Catanery Vulcanisation system (VCV) or horizontal MDCV will be used to ensure circularity and concentricity of the extruded layers around the conductor. CCV
3 Type of Cable: Cu/XLPE /PVC
4 Rated nominal voltage kV 6.6/12
5 Rated Maximum voltage kV 12
6 Nominal cross-sectional area of Conductor Sq.mm 50
7 Conductor
7.1 Material Copper
7.2  Shape & formation Round
7.3  Diameter of conductor  mm 8.3
7.4 Dia.Of Single Wire/Number of strands mm 2.98/7
8 Conductor Screen 
8.1 Material semi conductive material
8.2 Thickness of semi-conductor  screen mm 0.6
8.3 Diameter of Semi-conductor(Approx.) mm 9.5
9 Insulation
9.1 Material XLPE
9.2 Insulation Thickness(Min.Avg.) mm 3.4
9.3 Diameter of Insulation(Approx.) mm 16.3
10 Insulation Screen
10.1 Material Semi-conductive material
10.2 Insulation Screen Thickness(Approx.) mm 0.8
10.3 Diameter of Sime-Insulation(Approx.) mm 17.9
11  Metallic Screen:
11.1 Material Plain Annealed Copper Tape
11.2 Thickness of the copper tape screen mm 0.1
11.3  Diameter of the cable across the metallic screen(Approx.) mm 18.2
12 Filler
12.1 Material Non-hygroscopic Filler
12.2 Diameter of Laid-Up Core 39.3
13 Bedding tape
13.1  Material Nonwoven tape
13.2 Approximate thickness  mm 0.2
13.3 Diameter over of bedding (Approx.) mm 40.5
16 Outer Sheath
16.1 Material PVC
16.2 Outer Sheath Thickness(Nominal) 2.4
16.3 Over Diameter(Approx.) 45.3
17 Conductor Weight kg/km 1256
17.1 Total Cable Weight (Approx.) kg/km 2791
18 Minimum Bending Radius
18.1 During Installation mm 1800
18.2 Installed mm 1600
19 Maximum Pulling Tension
19.1 Of Conductor kN 10.5
20  Continuous current rating under the specified installation and operating conditions.    Conductor temperature 90° C    . Ground    temperature 25° C    and    depth    of laying 1000 mm
20.2 In Ground Amp 162
21 Maximum value of electric stresses at the conductor screen (Calculation to be shown separately)  kV/mm  2.57
21.1 Maximum value of dielectric stress at the insulation  kV/mm  1.5
22 Short circuit capacity of conductor for 1/2/3    second assuming    conductor temperature of 90 ° C prior to short    circuit and 250 ° C during short circuit
22.1 1.0 Secs kA 7.5
22.2 2.0 Secs kA 5.4
22.3 3.0 Secs kA 4.3
23 Short circuit capacity of metallic screen    for    1/2/3 second     at     screen temperature of 80 ° C prior to short circuit    and 200 ° C during short circuit
23.1 1.0 Secs kA 2.8
23.2 2.0 Secs kA 2.1
23.3 3.0 Secs kA 1.6
24 Screen voltage under maximum operating conditions assuming all circuits connected kV per km 0.05
25 TEST
25.1 Maximum D.C. resistance of conductor  per km. at 20 degree C.  Ohm 0.387
25.2 Maximum A.C. resistance of conductor per km. at 90 degree C.  Ohm 0.495
25.3  Maximum electrostatic capacitance per km. of cable. μF 0.238
25.4 Partial discharge at 1.50 Uo pc 10
25.5 A.C.  Enduring Test voltage 2.5U0/ hours  kV/mim 16.5/5
25.6 D.C.Out sheath  Enduring Test voltage  kV/mim 5kV/1min
25.7 Impulse test voltage kV 65
26 Approximate drum dimension (dia & width) mm/mm 2200*1400
27 Maximum length of cable in a drum (Metres) m 900
28 Minimum length of cable in a drum  (Metres) m 800
39 Approximate gross weight of cable in a drum  TON 2.6
30 Expected Cable life. Year 30

Drawing of Configuration

 Cu/XLPE/PVC 12 kV 3×50mm2



Cu/XLPE/PVC 12 kV   3×50mm2

Construction

Thickness(mm)

Diameter(mm)

1 --- Copper Conductor

 

 8.3(+0.1,-0.1)

2 --- Conductor screen

0.6

 9.5

3 --- XLPE insulation

3.4

 16.3(+0.5,-0.5)

4 --- Insulation screen

0.8

 17.9

5 --- Copper tape screen

0.1

 18.2

6 --- PP filler

 

39.3

7 --- Non-woven fabrics tape

0.2

 40.5

8--- PVC outer sheath

2.4

45.3(+2.0,-2.0)

 


Advanced Manufacturing Equipments

Product Equipment


 Advanced Testing Equipments  

      The company introduced the world's advanced level wire & cable production and testing equipment, such as DV-6E spectrum analyzer, online micro pore impurity tester, etc. 

        Advanced Testing Equipment     Guarantee High Quality Production

Test Equipment

 Packages

Packages 

  Our Honor

 We got trust and praise from all customers by outstanding quality and good reputation. To  providefirst-rate products and service for society is the pursuit of staffs of  our Company forever. The after-sale service department provides series of before-sale,selling and  after-sale, which solve the worries behind for customers and provide complete and rapid service  for customers. Customers' satisfaction is the best return for staffa of our Company.

Certificates


1.11kv Cable  2.Middle Voltage Power Cable  3.Five Core Copper Conductor   4.PVC Single Core Cable  5.Three Core Copper Conductor  

Product Categories : Copper Conductor Power Cable

Email to this supplier
  • *Subject:
  • *Messages:
    Your message must be between 20-8000 characters
Communicate with Supplier?Supplier
Crazy Zhang Mr. Crazy Zhang
What can I do for you?
Contact Supplier