Huayuan Gaoke Cable Co.,Ltd.
Double Nonmagnetic Steel Tape Armouring for Cable,FRLSOH PVC Outer Sheath For Cable,Semi-conducting Swelling Tape for Cable
Payment Type: | L/C,T/T,D/P,Western Union |
---|---|
Incoterm: | FOB,CFR,CIF,FCA,CPT |
Min. Order: | 500 Meter |
Model No.: YJV
Brand: HUAYUAN YONGTONG
Application: Construction
Voltage: Low and Medium Voltage Cable
Current: AC Cable
Insulation Material: XLPE
Sheath Material: Crosslinking
Material Shape: Round Wire
Wire Core Material: Bare Copper Wire
Certification: ISO
Brand: HUAYUAN YONGTONG
Packaging: Drums
Productivity: 100km/m
Transportation: Ocean,Land,Air
Place of Origin: BEIJING CHINA
Supply Ability: 100KM/M
Certificate: CE ISO CCC
HS Code: 8544601200
Port: Shanghai Port,Tianjin Port,Qingdao
Payment Type: L/C,T/T,D/P,Western Union
Incoterm: FOB,CFR,CIF,FCA,CPT
TECHNICLA DATA SHEET FOR 33 kV 1C 400 SQmm POWER CABLE
NO. | ITEM | UNIT | DATA |
1 | Name of Manufacturer: | Beijing Huayuan Gaoke | |
Cable Co.,Ltd. | |||
2 | Country of Manufacturer: | China | |
3 | Which type of manufacturing process viz. Continuous Catanery Vulcanisation (CCV) or vertical Catanery Vulcanisation system (VCV) or horizontal MDCV will be used to ensure circularity and concentricity of the extruded layers around the conductor. | VCV | |
4 | Type of Cable: | Cu/XLPE/CWS/PVC/STA/PVC | |
5 | Rated nominal voltage | kV | 19/33 |
6 | Rated Maximum voltage | kV | 36 |
7 | Nominal cross-sectional area of Conductor | Sq.mm | 400 |
8 | Conductor | ||
8.1 | Material | Copper | |
8.2 | Shape & formation | circular | |
8.3 | Diameter of conductor | mm | 23.8 |
8.4 | Dia.Of Single Wire/Number of strands | mm/ | 2.98/60 |
9 | Conductor Screen | ||
9.1 | Material | Semi conductor tape + semi conductive material | |
9.2 | Thickness of semi-conductor screen | mm | 0.12+0.8 |
9.3 | Diameter of Semi-conductor(Approx.) | mm | 25.8 |
10 | Insulation | ||
10.1 | Material | XLPE | |
10.2 | Insulation Thickness(Min.Avg.) | mm | 9.3 |
10.3 | Diameter of Insulation(Approx.) | mm | 44.5 |
11 | Insulation Screen | ||
11.1 | Material | Semi-conductive material | |
11.2 | Insulation Screen Thickness | mm | 0.8 |
11.3 | Diameter of Insulation screen(Approx.) | mm | 46.1 |
12 | Water Barrier | ||
12.1 | Material | semi-conducting water swellable tape | |
12.2 | Water barrier thickness((Nominal) | mm | 0.3 |
12.3 | Diameter of Insulation screen(Approx.) | mm | 47.4 |
13 | Metallic Screen: | ||
13.1 | Material | Copper wire+ copper tape | |
13.2 | Diameter of wire /NO. | mm/ | 0.8/50 |
13.3 | Thickness of tape/layer | mm/ | 0.1/1 |
13.4 | Cross section of the Metallic Screen | mm2 | 26 |
13.5 | Diameter of the cable across the metallic screen(Approx.) | mm | 49 |
14 | Bedding | ||
14.1 | Material | non-woven fabrics tape | |
14.2 | Approximate thickness (Nominal) | mm | 0.2 |
14.3 | Diameter of bedding tape (Approx.) | mm | 50 |
15 | Inner sheath | ||
15.1 | Material | PE laminated Aluminum tape. | |
15.2 | Thickness(Nominal) | mm | 0.2 |
15.3 | Diameter Over the inner sheath (Approx.) | mm | 51 |
16 | Armouring | ||
16.1 | Material | Nonmagnetic steel tape | |
16.2 | Thickness /layer | mm/ | 0.5/2 |
16.3 | Diameter (Approx.) | mm | 53 |
17 | Outer Sheath | ||
17.1 | Material | FRLSOH PVC | |
17.2 | Outer Sheath Thickness(Nominal) | 2.9 | |
17.3 | Over Diameter(Approx.) | 59 | |
18 | Conductor Weight | kg/km | 3542 |
18.1 | Total Cable Weight (Approx.) | kg/km | 6820 |
19 | Minimum Bending Radius | ||
19.1 | During Installation | mm | 900 |
19.2 | Installed | mm | 600 |
20 | Maximum Pulling Tension | ||
20.1 | Of Conductor | kN | 28 |
21 | Continuous current rating under the specified installation and operating conditions. Conductor temperature 90° C . Ground temperature 35° C and depth of laying 1500 mm | ||
21.1 | In Air | Amp | 629 |
21.2 | In Ground | Amp | 465 |
21.3 | In pipeline | Amp | 438 |
22 | Maximum value of electric stresses at the conductor screen (Calculation to be shown separately) | kV/mm | 2.72 |
22.1 | Maximum value of dielectric stress at the insulation | kV/mm | 1.57 |
23 | Short circuit capacity of conductor for 1/2/3 second assuming conductor temperature of 90 ° C prior to short circuit and 250 ° C during short circuit | ||
23.1 | 1.0 Secs | kA | 57.4 |
23.2 | 2.0 Secs | kA | 40.7 |
23.3 | 3.0 Secs | kA | 33.3 |
24 | Short circuit capacity of metallic screen for 1/2/3 second at screen temperature of 80 ° C prior to short circuit and 200 ° C during short circuit | ||
24.1 | 1.0 Secs | kA | 3.4 |
24.2 | 2.0 Secs | kA | 2.4 |
24.3 | 3.0 Secs | kA | 2 |
25 | Screen voltage under maximum operating conditions assuming all circuits connected | kV per km | 0.05 |
26 | TEST | ||
26.1 | Maximum D.C. resistance of conductor per km. at 20 degree C. | Ohm | 0.047 |
26.2 | Maximum A.C. resistance of conductor per km. at 90 degree C. | Ohm | 0.0614 |
26.3 | Maximum electrostatic capacitance per km. of cable. | μF | 0.233 |
26.4 | Partial discharge at 1.50 Uo | pc | ≤ 10 |
26.5 | A.C. Enduring Test voltage 2.5U0/ hours | kV/mim | May-70 |
26.6 | D.C.Out sheath Enduring Test voltage | kV/mim | 5kV/1min |
26.7 | Impulse test voltage | kV | 170 |
27 | Approximate drum dimension (dia & width) | mm/mm | 2200*1400 |
28 | Maximum length of cable in a drum (Metres) | m | 600 |
28.1 | Minimum length of cable in a drum (Metres) | m | 500 |
29 | Approximate gross weight of cable in a drum | TON | 4.3 |
30 | Expected Cable life. | Year | 30 |
Drawing of Configuration
CU/XLPE/CWS/PVC/STA/PVC 19/33(36) kV 1C 400 mm2
Construction | Thickness(mm) | Diameter(mm) |
1 --- Copper conductor |
| 23.8(+0.2,-0.2) |
2 --- Semi conductor tape +conductor screen | 0.12+0.8 | 25.8 |
3 --- Insulation | 9.3 | 44.5(+0.5,-0.5) |
4 --- Insulation screen | 0.8 | 46.1 |
5 ---Semi-conducting swelling tape | 0.3 | 47.4 |
6 --- Copper wires +Copper tape | 0.8+0.1 | 49.0 |
7 ---Inner shearh(bedding tape+ PE laminated Aluminum tape.) | 0.2+0.2 | 51.0 |
8 --- Double nonmagnetic steel tape armouring | 0.5 | 53.0 |
9 ---FRLSOH PVC outer sheath | 2.9 | 59.0(+2.0,-2.0) |
Drum
d1:2200mm
L1:1400mm
500m per drum
H :2200mm
L :2200mm
W:1400mm
Wight: 200 kg
Advanced Manufacturing Equipments
Advanced Testing Equipments
The company introduced the world's advanced level wire & cable production and testing equipment, such as DV-6E spectrum analyzer, online micro pore impurity tester, etc.
Advanced Testing Equipment Guarantee High Quality Production
1.33kv Cable 2.Middle Voltage Power Cable 3.Steel Wire Armoured Cable 4.Steel Tape Armoured 5.Three Core Copper Conductor 6.Copper Fire Cable
Product Categories : Copper Conductor Power Cable