Huayuan Gaoke Cable Co.,Ltd.
Replacing Oil Filled Paper Inuslated Cable,Installed in Tunnel Pipeline Direct Burial Power Cable,Tested in Member from STL Lab for Cable
Unit Price: | USD 90 / Meter |
---|---|
Payment Type: | L/C,T/T,D/P,Paypal,Money Gram,Western Union |
Incoterm: | FOB,CFR,CIF,FCA,CPT |
Min. Order: | 1000 Meter |
Delivery Time: | 35 Days |
Model No.: YJLW02
Brand: HUYUAN YONGTONG
Type: Insulated
Conductor Type: Stranded
Application: Underground
Conductor Material: Copper
Sheath Material: Crosslinking
Insulation Material: XLPE
Material Shape: Round Wire
Range of Application: LSOH
Certification: CCC
Brand: HUAYUAN YONGTONG
Packaging: DRUM
Productivity: 2000KM/YEAR
Transportation: Ocean,Land,Air
Place of Origin: CHINA
Supply Ability: 100KM/MONTH
Certificate: CE,CCC,ISO
HS Code: 8544601400
Port: Tianjin Port,Shanghai Port,Qingdao Port
Payment Type: L/C,T/T,D/P,Paypal,Money Gram,Western Union
Incoterm: FOB,CFR,CIF,FCA,CPT
Delivery Time: 35 Days
Aluminium Amoured High Voltage Cable 220kv 1c2500sqmm Xlpe Insulated Corrugated
Brief introduction of the 110~220KV XLPE high-voltage cable products
1. The cross-linkage PE insulated and wrinkled aluminum wrapper waterproof PVC Sheathed Power Cable.
Type | YJLW02,YJLLW02 |
Specification | 240mm2~3000mm2 |
Voltage | 110~220KV |
Usage | Suitable for damp areas and the places with a lower underground water level and to be used underground, in tunnels or pipes. Such cables bear a bigger pulling force and pressure. |
2. The cross-linkage PE insulated and wrinkled aluminum wrapper waterproof PE sheathed power cable.
Type | YJLW03,YJLLW03 |
Specification | 240mm2~3000mm2 |
Voltage | 110~220KV |
Usage | Suitable for the places with a higher underground water level and to be used underground, in the tunnels or pipes. Such cables bear a bigger pulling force and pressure. |
Cable type
Bending diameter | Metal sheathed |
After laying | 30D0 |
During laying | 40D0 |
Note: In form, D0 is a real test value to cable`s outer diameter.
The single core cable is required P≤500kg/m.
P=T/R (T is indicated axial traction force; R is indicated radius of bent-wheel), Knowing from above formula, as the traction force is made up by length and weight of cable. So it lets P to applying requirement as above. Then the diameter of bent-wheel should be widened.
Type: YJLW02(or YJLW03) Specifications: 1×240mm2~1×1200mm2 | |||||||
Conductor section mm2 | Conductor diameter mm | Insulator thickness mm | Aluminum wrapper mm | Sheath thickness mm | Cable`s outer diameter mm | kg/km Cable`s weight | |
PVC sheath | PE sheath | ||||||
240 | 18.4 | 19.0 | 2.0 | 4.5 | 89.9 | 8348 | 7708 |
300 | 20.6 | 18.5 | 2.0 | 4.5 | 91.1 | 8990 | 8341 |
400 | 23.8 | 17.5 | 2.0 | 4.5 | 92.3 | 9731 | 9073 |
500 | 26.6 | 17.0 | 2.0 | 4.5 | 94.5 | 10882 | 10208 |
630 | 30.0 | 16.5 | 2.0 | 4.5 | 96.9 | 12352 | 11660 |
800 | 34.0 | 16.0 | 2.0 | 4.5 | 99.9 | 14168 | 13454 |
1000 | 38.2 | 16.0 | 2.0 | 4.5 | 105.0 | 16460 | 15708 |
1200 | 42.6 | 16.0 | 2.0 | 4.5 | 109.4 | 18685 | 17900 |
Conductor section mm2 | (Ω/km) Conductor resistance | CapacitanceμF/km | Carrier current capacity A | Short circuit current | ||
20℃DC | 90℃AC | Conductor | Metal sheath | |||
240 | 0.0754 | 0.0961 | 0.135 | 543 | 20 | 22 |
300 | 0.0601 | 0.0766 | 0.146 | 597 | 25 | 22 |
400 | 0.0470 | 0.0599 | 0.165 | 657 | 33 | 22 |
500 | 0.0366 | 0.0467 | 0.182 | 718 | 41 | 23 |
630 | 0.0283 | 0.0361 | 0.201 | 779 | 52 | 24 |
800 | 0.0221 | 0.0282 | 0.223 | 837 | 66 | 25 |
1000 | 0.0176 | 0.0224 | 0.246 | 914 | 83 | 26 |
1200 | 0.0151 | 0.0193 | 0.266 | 962 | 99 | 27 |
Note: Current carrier capacity is made up by laying in soil abreast. The axial distances between cables are 200mm. Soil temperature is 25℃. The working temperature of cable is 90℃. The coefficient of soil heat-resistance is 1.2km/W.
Type: YJLW02(or YJLW03) Specifications: 1×400mm2~1×2500mm2 | |||||||
Conductor section mm2 | Conductor diameter mm | Insulator thickness mm | Aluminum wrapper mm | Sheath thickness mm | Cable`s outer diameter mm | kg/km Cable`s weight | |
PVC sheath | PE sheath | ||||||
400 | 23.8 | 27 | 2.4 | 5.0 | 128.7 | 14348 | 13369 |
500 | 26.6 | 27 | 2.4 | 5.0 | 131.5 | 15697 | 14696 |
630 | 30.0 | 26 | 2.4 | 5.0 | 132.8 | 17064 | 16052 |
800 | 34.0 | 25 | 2.5 | 5.0 | 134.9 | 18913 | 17885 |
1000 | 38.2 | 24 | 2.5 | 5.0 | 137.7 | 20966 | 19918 |
1200 | 42.6 | 24 | 2.6 | 5.0 | 142.3 | 23459 | 22372 |
1400 | 46.1 | 24 | 2.6 | 5.0 | 145.8 | 25712 | 24598 |
1600 | 49.2 | 24 | 2.7 | 5.0 | 149.1 | 28039 | 26899 |
1800 | 52.1 | 24 | 2.7 | 5.0 | 152.0 | 30214 | 29050 |
2000 | 55.2 | 24 | 2.8 | 5.0 | 155.3 | 32548 | 31359 |
2200 | 57.5 | 24 | 2.8 | 5.0 | 157.6 | 34643 | 33436 |
2500 | 61.2 | 24 | 2.9 | 5.0 | 161.5 | 37958 | 36719 |
Conductor section mm2 | (Ω/km) Conductor resistance | CapacitanceμF/km | Carrier current capacity A | (KA/3S) Short circuit current | ||
20℃DC | 90℃AC | Conductor | Metal sheath | |||
400 | 0.0470 | 0.0613 | 0.120 | 689 | 33 | 46 |
500 | 0.0366 | 0.0485 | 0.127 | 763 | 41 | 47 |
630 | 0.0283 | 0.0384 | 0.139 | 839 | 52 | 48 |
800 | 0.0221 | 0.0311 | 0.153 | 918 | 66 | 51 |
1000 | 0.0176 | 0.0232 | 0.173 | 1014 | 83 | 52 |
1200 | 0.0151 | 0.0201 | 0.182 | 1082 | 99 | 56 |
1400 | 0.0129 | 0.0174 | 0.191 | 1136 | 116 | 58 |
1600 | 0.0113 | 0.0156 | 0.200 | 1192 | 132 | 62 |
1800 | 0.0101 | 0.0142 | 0.208 | 1232 | 149 | 63 |
2000 | 0.0090 | 0.0128 | 0.217 | 1282 | 165 | 67 |
2200 | 0.0083 | 0.0121 | 0.223 | 1310 | 182 | 68 |
2500 | 0.0073 | 0.0110 | 0.233 | 1367 | 206 | 73 |
Note: Current carrier capacity is made up by laying in soil abreast. The axial distance between cables are 200mm. Soil temperature is 25℃. The working temperature of cable is 90℃. The coefficient of soil heat-resistance is 1.2km/W.
1.High Voltage Power Cable 2.230kv XLPE Cable 3.Steel Wire Armoured Cable 4.Steel Tape Armoured 5.Single Core Aluminium Conductor 6.Aluminium Corrugated Cable
Looking for ideal Replacing Oil Filled Paper Inuslated Cable Manufacturer & supplier ? We have a wide selection at great prices to help you get creative. All the Installed in Tunnel Pipeline Direct Burial Power Cable are quality guaranteed. We are China Origin Factory of Tested in Member from STL Lab for Cable. If you have any question, please feel free to contact us.Product Categories : High Voltage Power Cable