http://www.bjhygkcable.com
Home > Products > Low Voltage Power Cable > 0.6/1kv copper conductor XLPE insulated PVC sheath

0.6/1kv copper conductor XLPE insulated PVC sheath

    Payment Type: L/C,T/T,Western Union
    Incoterm: FOB,CFR,CIF,FCA,CPT,CIP
    Min. Order: 1000 Meter
    Delivery Time: 30 Days
Basic Info

Model No.: YJV

Type: Insulated

Conductor Type: Stranded

Application: Underground, Heating, Overhead

Conductor Material: Copper

Sheath Material: Crosslinking

Insulation Material: XLPE

Material Shape: Round Wire

Certification: VDE, RoHS, CCC, UL, CE, ISO9001

Brand: HUAYUAN YONGTONG

Range of Application: Flame Retardant

Additional Info

Packaging: Drum

Productivity: 1000km/M

Brand: HUAYUAN YONGTONG

Transportation: Ocean,Land,Air

Place of Origin: Beijing,China

Supply Ability: 1000km/M

Certificate: CE,CCC,ISO

HS Code: 8544601200

Port: Tianjin Port,Shanghai Port,Qingdao Port

Product Description

1. APPLICALBE STANDARDS

The cable which Beijing Huayuan Gaoke Cable Co.,Ltd. offered shall be designed, manufactured and tested according to international standards as follows:

Quality Control Standard

ISO 9001

Quality Management Systems

ISO 14001

Environmental Management Systems

Component Material Standard

IEC 60228

Conductors of insulated cables

Cable Standard

IEC 60502-1

Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) –

Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3kV(Um=3.6kV)

Fire retardant according to IEC/EN 60332-3-24

2.
CABLES STRUCTURE XLPE CABLE

1)

PVC1

CU/XLPE/PVC 0.6/1 kV 1×50 mm2

Construction

Nominal Thickness(mm)

Nominal Diameter(mm)

1-Stranded compacted circular

copper conductor

/

8.1

2 XLPE insulation

1.0

10.1

3-FR-PVC Outer sheath

1.4

12.9

2)

PVC2

CU/XLPE/PVC 0.6/1kV 1×95 mm2

Construction

Nominal Thickness(mm)

Nominal Diameter(mm)

1-Stranded compacted circular

copper conductor

/

11.5

2 XLPE insulation

1.1

13.7

3-FR-PVC Outer sheath

1.5

16.7

3)

PVC3

CU/XLPE/PVC 0.6/1kV 4×16 mm2

Construction

Nominal Thickness(mm)

Nominal Diameter(mm)

1-Stranded non-compacted circular

copper conductor

/

5.0

2 XLPE insulation

0.7

6.4

3 Filling

/

15.5

4 Wrapping tape

0.2

16.1

5-FR-PVC Outer sheath

1.8

19.7

4)

PVC4

CU/XLPE/PVC 0.6/1kV 4×25 mm2

Construction

Nominal Thickness(mm)

Nominal Diameter(mm)

1-Stranded compacted circular

aluminum conductor

/

5.9

2 XLPE insulation

0.9

7.7

3 Filling

/

18.6

4 Wrapping tape

0.2

19.2

5-FR-PVC Outer sheath

1.8

22.8

3. Guaranteed Technical Particulars

1) CU/XLPE/PVC 0.6/1 kV 1×50 mm2

No

DESCRIPTION

UNIT

VALUEREQUIRED

1

Manufacturer

BEIJING HUAYUAN

2

Cable size

mm2

50

3

Cable type

CU/XLPE/PVC

4

Voltage Grade

kV

0.6/1(1.2)

5

Reference Standard

IEC 60228 IEC 60502.1

6

No. and cross sectional area of conductor

1×50mm2

7

Conductor material

Copper

8

Shape

stranded compacted circular

9

Nominal diameter of conductor

mm

8.1

10

Insulation material

XLPE

Colour

gray

11

Nominal thickness of insulation

mm

1.0

12

Nominal diameter over insulation

mm

10.1

13

Inner sheath material

NA

14

Nominal thickness of inner sheath

mm

NA

15

Outer sheath material

ultraviolet-proof-FR-PVC

Colour

gray

16

Nominal thickness of outer sheath

mm

1.4

17

Nominal overall diameter of cable

mm

12.9

18

Short circuit current rating(t=1.0sec)

Of conductor

kA

7.3(max)

19

Max. conductor temperature in short circuit

250(not exceed 5s)

20

Approx. weight of cable

kg/km

458

21

Minimum bending radius

mm

230

22

Max.D.C. Conductor resistanceat20`C

Ω/km

0.387

23

Max. conductor temperature on continuous

90

24

Max. current rating in air

A

325( temperature 40° C , 1 circuit, flat formation, phase distance 2 diameter of cable)

25

Max. current rating in tunnel

A

230(depth of laying 1000 mm ,thermal resistivity of soil 1.2 k.m/W,temperature 25℃, flat formation, phase distance 2 diameter of cable)

2) CU/XLPE/PVC 0.6/1kV 1×95 mm2

No

DESCRIPTION

UNIT

VALUEREQUIRED

1

Manufacturer

BEIJING HUAYUAN

2

Cable size

mm2

95

3

Cable type

CU/XLPE/PVC

4

Voltage Grade

kV

0.6/1(1.2)

5

Reference Standard

IEC 60228 IEC 60502.1

6

No. and cross sectional area of conductor

1×95mm2

7

Conductor material

Copper

8

Shape

stranded compacted circular

9

Nominal diameter of conductor

mm

11.5

10

Insulation material

XLPE

Colour

gray

11

Nominal thickness of insulation

mm

1.1

12

Nominal diameter over insulation

mm

13.7

13

Inner sheath material

NA

14

Nominal thickness of inner sheath

mm

NA

15

Outer sheath material

ultraviolet-proof-FR-PVC

Colour

gray

16

Nominal thickness of outer sheath

mm

1.5

17

Nominal overall diameter of cable

mm

16.7

18

Short circuit current rating(t=1.0sec)

Of conductor

kA

13.8(max)

19

Max. conductor temperature in short circuit

250(not exceed 5s)

20

Approx. weight of cable

kg/km

919

21

Minimum bending radius

mm

300

22

Max.D.C. Conductor resistanceat20`C

Ω/km

0.193

23

Max. conductor temperature on continuous

90

24

Max. current rating in air

A

370( temperature 40° C , 1 circuit, flat formation, phase distance 2 diameter of cable)

25

Max. current rating in tunnel

A

335(depth of laying 1000 mm ,thermal resistivity of soil 1.2 k.m/W,temperature 25℃, flat formation, phase distance 2 diameter of cable)

3) CU/XLPE/PVC 0.6/1kV 4×16 mm2

No

DESCRIPTION

UNIT

VALUEREQUIRED

1

Manufacturer

BEIJING HUAYUAN

2

Cable size

mm2

16

3

Cable type

CU/XLPE/PVC

4

Voltage Grade

kV

0.6/1(1.2)

5

Reference Standard

IEC 60228 IEC 60502.1

6

No. and cross sectional area of conductor

4×16mm2

7

Conductor material

Copper

8

Shape

stranded non-compacted circular

9

Nominal diameter of conductor

mm

5.1

10

Insulation material

XLPE

Colour

Black, Blue, Brown, Gray

11

Nominal thickness of insulation

mm

0.7

12

Nominal diameter over insulation

mm

6.4

13

Inner sheath material

NA

14

Nominal thickness of inner sheath

mm

NA

15

Outer sheath material

ultraviolet-proof-FR-PVC

Colour

gray

16

Nominal thickness of outer sheath

mm

1.8

17

Nominal overall diameter of cable

mm

19.7

18

Short circuit current rating(t=1.0sec)

Of conductor

kA

2.4(max)

19

Max. conductor temperature in short circuit

250(not exceed 5s)

20

Approx. weight of cable

kg/km

721

21

Minimum bending radius

mm

300

22

Max.D.C. Conductor resistanceat20`C

Ω/km

1.15

23

Max. conductor temperature on continuous

90

24

Max. current rating in air

A

75( temperature 40° C , 1 circuit, flat formation, phase distance 2 diameter of cable)

25

Max. current rating in tunnel

A

92(depth of laying 1000 mm ,thermal resistivity of soil 1.2 k.m/W,temperature 25℃, flat formation, phase distance 2 diameter of cable)


4) CU/XLPE/PVC 0.6/1kV 4×25 mm2

No

DESCRIPTION

UNIT

VALUEREQUIRED

1

Manufacturer

BEIJING HUAYUAN

2

Cable size

mm2

25

3

Cable type

CU/XLPE/PVC

4

Voltage Grade

kV

0.6/1(1.2)

5

Reference Standard

IEC 60228 IEC 60502.1

6

No. and cross sectional area of conductor

4×25mm2

7

Conductor material

Copper

8

Shape

stranded compacted circular

9

Nominal diameter of conductor

mm

5.9

10

Insulation material

XLPE

Colour

Black, Blue, Brown, Gray

11

Nominal thickness of insulation

mm

0.9

12

Nominal diameter over insulation

mm

7.7

13

Inner sheath material

NA

14

Nominal thickness of inner sheath

mm

NA

15

Outer sheath material

ultraviolet-proof-FR-PVC

Colour

gray

16

Nominal thickness of outer sheath

mm

1.8

17

Nominal overall diameter of cable

mm

22.8

18

Short circuit current rating(t=1.0sec)

Of conductor

kA

3.7(max)

19

Max. conductor temperature in short circuit

250(not exceed 5s)

20

Approx. weight of cable

kg/km

1063

21

Minimum bending radius

mm

340

22

Max.D.C. Conductor resistanceat20`C

Ω/km

0.727

23

Max. conductor temperature on continuous

90

24

Max. current rating in air

A

92( temperature 40° C , 1 circuit, flat formation, phase distance 2 diameter of cable)

25

Max. current rating in tunnel

A

126(depth of laying 1000 mm ,thermal resistivity of soil 1.2 k.m/W,temperature 25℃, flat formation, phase distance 2 diameter of cable)


4. TEST REQUIREMENTS FOR LV POWER CABLES

The cable testing shall be conducted in accordance with applicable standard of 0.6/1kV Power Cables. The following test items shall be carried out in accordance with relevant IEC standards.

No.

Test item

Routine tests

1

measurement of the electrical resistance of conductors

2

Voltage test

Sample tests

1

conductor examination

2

check of dimensions

3

Hot set test for XLPE insulation


5. PACKING PARTICULARS FOR 0.6/1 kV POWER CABLE

The cables shall be wound on steel-wooden drums. The indelible marking shall be printed on the surface of drum flange in accordance with customer requirements.

packagepackage1

Cable Type

Drum length(m)

Drum Dimensions (mm)

D

d

L2

L1

CU/XLPE/PVC 0.6/1kV-1C*50mm2

1000

1000

450

450

550

CU/XLPE/PVC 0.6/1kV-1C*95mm2

1000

1250

690

580

700

CU/XLPE/PVC 0.6/1kV-4C*16mm2

500

1250

690

580

700

CU/XLPE/PVC 0.6/1kV-4C*25mm2

500

1250

690

580

700

Note: The value [D" shall not contain the dimension of sealing plates.


Our Fantory

undefinedundefined

Package

undefined

Delivery

undefinedundefined

Honor

undefined

The voltage of the Fire Alarm Cable, Security Fire Alarm Cable, Fire-Proof Cable, Fire resistance cable all could be 0.6/1kv Cable or 1kv cable or 0.6kv Cable.

Looking for ideal 1x50 Mm2 Low Voltage Power Cable Manufacturer & supplier ? We have a wide selection at great prices to help you get creative. All the 1x95 Mm2 Single Core Power Cable are quality guaranteed. We are China Origin Factory of Ultraviolet-proof Outer Sheath Power Cable. If you have any question, please feel free to contact us.

Product Categories : Low Voltage Power Cable

Email to this supplier
  • *Subject:
  • *Messages:
    Your message must be between 20-8000 characters
Communicate with Supplier?Supplier
Crazy Zhang Mr. Crazy Zhang
What can I do for you?
Chat Now Contact Supplier