http://www.bjhygkcable.com
Home > Products > Middle Voltage Power Cable > 36KV 3*70sqmm Copper Conductor XLPE Power Cable

36KV 3*70sqmm Copper Conductor XLPE Power Cable

    Payment Type: L/C,T/T,D/P,Western Union
    Incoterm: FOB,CFR,CIF,FCA,CPT
    Min. Order: 500 Meter
    Delivery Time: 30 Days
Basic Info

Model No.: NA2XS2Y

Type: Insulated

Conductor Type: Stranded

Application: Underground

Conductor Material: Copper

Sheath Material: PVC

Insulation Material: XLPE

Range of Application: LSOH

Certification: VDE, RoHS, CCC, UL, CE, ISO9001

Brand: HUAYUAN YONGTONG

Material Shape: Round Wire

Additional Info

Packaging: Drums

Productivity: 100KM/M

Brand: HUAYUAN YONGTONG

Transportation: Ocean,Land,Air

Place of Origin: BEIJING CHINA

Supply Ability: 100KM/M

Certificate: CE ISO CCC

HS Code: 8544601300

Port: Shanghai Port,Tianjin Port,Qingdao Port

Product Description

TECHNICLA DATA SHEET FOR 36 kV 3C 70 SQmm POWER CABLE

NO. ITEM UNIT DATA
1 Name of Manufacturer: Beijing Huayuan Gaoke
Cable Co.,Ltd.
1.2 Country of Manufacturer: China
2 Which type of manufacturing process viz. Continuous Catanery Vulcanisation (CCV) or vertical Catanery Vulcanisation system (VCV) or horizontal MDCV will be used to ensure circularity and concentricity of the extruded layers around the conductor. CCV
3 Type of Cable: Cu/XLPE/AWA/PVC
4 Rated nominal voltage kV 20/36
5 Rated Maximum voltage kV 36
6 Nominal cross-sectional area of Conductor Sq.mm 70
7 Conductor
7.1 Material Copper
7.2 Shape & formation Round
7.3 Diameter of conductor mm 10.0
7.4 Dia.Of Single Wire/Number of strands mm 2.17/19
8 Conductor Screen
8.1 Material semi conductive material
8.2 Thickness of semi-conductor screen mm 0.8
8.3 Diameter of Semi-conductor(Approx.) mm 11.6
9 Insulation
9.1 Material XLPE
9.2 Insulation Thickness(Min.Avg.) mm 8.0
9.3 Diameter of Insulation(Approx.) mm 27.6
10 Insulation Screen
10.1 Material Semi-conductive material
10.2 Insulation Screen Thickness(Approx.) mm 1.0
10.3 Diameter of Sime-Insulation(Approx.) mm 29.2
11 Metallic Screen:
11.1 Material Plain Annealed Copper Tape
11.2 Thickness of the copper tape screen mm 0.10
11.3 Diameter of the cable across the metallic screen(Approx.) mm 29.5
12 Filler
12.1 Material Non-hygroscopic Filler
12.2 Diameter of Laid-Up Core 63.7
13 Bedding tape
13.1 Material Nonwoven tape
13.2 Approximate thickness mm 0.2
13.3 Diameter over of bedding (Approx.) mm 68.4
14 Inner Sheath
14.1 Material PVC
14.2 Inner Sheath Thickness(Nominal) 1.9
14.3 Diameter over the Inner sheath(Approx.) 68.7
15 Armouring
15.1 Material Steel tape
15.2 Approximate diameter or thickness mm/ 0.5
15.3 Diameter of armouring (Approx.) mm 70.7
16 Outer Sheath
16.1 Material PVC
16.2 Outer Sheath Thickness(Nominal) 3.4
16.3 Over Diameter(Approx.) 77.5
17 Conductor Weight kg/km 1804
17.1 Total Cable Weight (Approx.) kg/km 7650
18 Minimum Bending Radius
18.1 During Installation mm 1500
18.2 Installed mm 1200
19 Maximum Pulling Tension
19.1 Of Conductor kN 14.7
20 Continuous current rating under the specified installation and operating conditions. Conductor temperature 90° C . Ground temperature 25° C and depth of laying 1000 mm
20.2 In Ground Amp 245
21 Maximum value of electric stresses at the conductor screen (Calculation to be shown separately) kV/mm 3.98
21.1 Maximum value of dielectric stress at the insulation kV/mm 1.67
22 Short circuit capacity of conductor for 1/2/3 second assuming conductor temperature of 90 ° C prior to short circuit and 250 ° C during short circuit
22.1 1.0 Secs kA 10.0
22.2 2.0 Secs kA 7.1
22.3 3.0 Secs kA 5.8
23 Short circuit capacity of metallic screen for 1/2/3 second at screen temperature of 80 ° C prior to short circuit and 200 ° C during short circuit
23.1 1.0 Secs kA 4.5
23.2 2.0 Secs kA 3.2
23.3 3.0 Secs kA 2.8
24 Screen voltage under maximum operating conditions assuming all circuits connected kV per km 0.05
25 TEST
25.1 Maximum D.C. resistance of conductor per km. at 20 degree C. Ohm 0.268
25.2 Maximum A.C. resistance of conductor per km. at 90 degree C. Ohm 0.34
25.3 Maximum electrostatic capacitance per km. of cable. μF 0.148
25.4 Partial discharge at 1.50 Uo pc 10
25.5 A.C. Enduring Test voltage 2.5U0/ hours kV/mim 70/5
25.6 D.C.Out sheath Enduring Test voltage kV/mim 5kV/1min
25.7 Impulse test voltage kV 170
26 Approximate drum dimension (dia & width) mm/mm 2800*1700
27 Maximum length of cable in a drum (Metres) m 600
28 Minimum length of cable in a drum (Metres) m 500
39 Approximate gross weight of cable in a drum TON 4.2
30 Expected Cable life. Year 30

Cu/XLPE/STA/PVC 20/36 kV 3×70mm2



Cu/XLPE/STA/PVC 20/36 kV 3×70mm2

Construction

Thickness(mm)

Diameter(mm)

1 --- Copper Conductor

10.0(+0.1,-0.1)

2 --- Conductor screen

0.8

11.6

3 --- XLPE insulation

8.0

27.6(+0.8,-0.5)

4 --- Insulation screen

1.0

29.2

5 --- Copper tape screen

0.1

29.5

6 --- PP filler

63.7

7 --- Non-woven fabrics tape

0.2

64.9

8 --- PVC inner sheath

1.9

68.7(+1.5,-1.5)

9 --- Steel tape armour

0.5

70.7

10--- PVC outer sheath

3.4

77.5(+2.5,-2.0)




Advanced Manufacturing Equipments

91 DRUMS COPPER WIRES STRANDING LINES132KV AND BELOW XLPE EXTRUDING LINE ONERoutine Test Hall

Product Equipment


Advanced Testing Equipments

The company introduced the world's advanced level wire & cable production and testing equipment, such as DV-6E spectrum analyzer, online micro pore impurity tester, etc.

Advanced Testing Equipment Guarantee High Quality Production

Test Equipment


Foreign Customers in our Factory

Packages

Packages

Our Honor

We got trust and praise from all customers by outstanding quality and good reputation. To providefirst-rate products and service for society is the pursuit of staffs of our Company forever. The after-sale service department provides series of before-sale,selling and after-sale, which solve the worries behind for customers and provide complete and rapid service for customers. Customers' satisfaction is the best return for staffa of our Company.

Certificates



1.High Voltage Power Cable 2.HV XLPE Cable 3.33kv Cable 4.High Quality 3 Core Power Cable 5.Fice Core Copper Conductor 6.Three Core Copper Conductor

Looking for ideal Copper Conductor XLPE Insulation PP Filler Manufacturer & supplier ? We have a wide selection at great prices to help you get creative. All the NA2XS2Y N2XS2Y Cable are quality guaranteed. We are China Origin Factory of Copper Tape Screen PVC Outer Sheath for Cable. If you have any question, please feel free to contact us.

Product Categories : Middle Voltage Power Cable

Email to this supplier
  • *Subject:
  • *Messages:
    Your message must be between 20-8000 characters
Communicate with Supplier?Supplier
Crazy Zhang Mr. Crazy Zhang
What can I do for you?
Chat Now Contact Supplier