http://www.bjhygkcable.com
Home > Products > Overhead Cable > ACAR 750 MCM Overhead Transmission Line Conductor

ACAR 750 MCM Overhead Transmission Line Conductor

    Payment Type: L/C,T/T,D/P,Paypal,Money Gram,Western Union
    Incoterm: FOB,CFR,CIF,FCA,CPT,CIP
    Min. Order: 1000 Meter
    Delivery Time: 30 Days
Basic Info

Model No.: ACAR

Brand: HUAYUAN YONGTONG

Additional Info

Packaging: Drum

Productivity: 1000km/M

Brand: HUAYUAN YONGTONG

Transportation: Ocean,Land,Air

Place of Origin: Beijing,China

Supply Ability: 1000km/M

Certificate: CE,CCC,ISO

Port: Tianjin Port,Shanghai Port,Qingdao Port

Product Description

Technical Specifications to the Phase Conductor

1) CSC-NPA-LT-NPAPA- HCTEM-0001

2) CSC-NPA-LT-NPACON- HCTEM-0001

3) CSC-NPA-LT-NPAPAR- HCTEM-0001

ITÉM

FEATURES

UNIT

REQUESTED

GUARANTEED

1

MANUFACTURER

1.1

Name

-

indicate

Beijing Huayuan

1.2

Country

-

indicate

CHINA

2

COMPLETE CONDUCTOR FEATURES

2.1

Conductor type

-

ACAR

ACAR

2.2

Standards that fulfill

-

ASTM B-524

ASTM B-524

2.3

Nominal Cross section

mm2

380

380

2.4

Nominal external diameter

mm

25.31

25.31

2.5

Nominal unit weight

kg/km

1047

1049

2.6

Minimum breaking strength

kg

7056

7056

2.7

Number of wires

each

30/7

30/7

2.8

Elasticity module

· Initial

kg/mm2

indicate

5700

· Final

kg/mm2

indicate

5700

2.9

Linear expansion Coefficient

1/°C

23 x 10-6

23 x 10-6

2.1

A.C. Electrical resistance , 50 hz ,at 25 °C

Ω/km

indicate

≤0.09795

2.11

Coefficient of variation of electrical resistance with temperature.

1/°C

indicate

0.00403

2.12

Reactance at 1 foot and 50 Hz

· Inductive

Ω/km

indicate

0.233

· Capacitive

Ω/km

indicate

/

2.13

Geometric Mean Radius

mm

indicate

/

3

ALUMINUM ALLOY WIRES

3.1

Standards that fulfill

-

ASTM B-398

ASTM B-398

3.2

Nominal diameter

mm

3.62

3.62

3.3

Minimum Conductivity at 20°C, 50 Hz

% IACS

indicate

53.5

3.4

Minimum average breaking strength

· before wiring

MPa

indicate

315

· after wiring

MPa

indicate

302

3.5

Minimum average elongation at 254 mm

· before wiring

%

indicate

3

· after wiring

%

indicate

2

3.6

Type of welding and welding wire treatment

-

indicate

cold welding

3.7

Minimum tensile strength on welded wire

MPa

indicate

302

3.8

Elasticity module

MPa

indicate

56000

3.9

Linear expansion Coefficient

1/°C

23 x 10-6

23 x 10-6

3.1

Chemical composition

· Aluminum, mínimum

% Peso

indicate

97.28

· Copper, máximum

% Peso

indicate

0.1

· iron , máximum

% Peso

indicate

0.5

· Silicon , range

% Peso

indicate

0.50-0.9

· Manganese, máximum

% Peso

indicate

0.03

· Magnesium, máximum range

% Peso

indicate

0.6-0.9

· Zinc, máximum

% Peso

indicate

0.10

· Chromo, máximum

% Peso

indicate

0.03

· Boron, máximum

% Peso

indicate

0.06

· Others elements, máximum

% Peso

indicate

0.10

4

REELS

4.1

Nominal length of the continuous cable strip

m

2000

2000

4.2

Reel gross weight , including OPGW cable and lathing

kg

indicate

2298(including ACAR )

4.3

External diameter over lathing

cm

indicate

180

4.4

Flange diameter

cm

indicate

180

4.5

Drum diameter

cm

indicate

180

4.6

Inside width , between flanges

cm

indicate

940

4.7

External width

cm

indicate

1100

4.8

Hole diameter for axis

cm

indicate

160

4.9

Number of bolts of flanges

-

indicate

8

4.1

Material from which the reel is made

-

indicate

TBEA

5

QUANTITIES

5.1

ACAR CONDUCTOR

km

1830

1830

6

TESTS

6.1

Test list

-

indicate

YES

6.2

Test Protocols

-

indicate

YES

6.3

Period of tests in factory

-

indicate

YES

7

DELIVERY TIME

7.1

Delivery date certified information

-

indicate

7.2

Delivery term

-

indicate

7.3

Certified information, catalogs, plans, etc.

-

indicate

7.4

Gantt chart

-

indicate

Conductor Structure for ACAR 750 MCM

ACAR 750 mcm

Construction

Nominal NO./Diameter(mm)

Nominal Diameter(mm)

1--- Aluminum Alloy Wire

7 / 3.62

10.86

2--- Aluminum Wire

30 / 3.62

25.34


Test Requirements for Overhead Conductor

The following test items shall be carried out in accordance with relevant ASTM standards.

No.

Test item

Tests(The user has no special requirements)

1

Tensile Strength and Elongation Requirements (test frequency 10%)Before strands

2

Resistivity test(test frequency 10%)

3

Structural inspection(test frequency 10%)

Factory and equipment

XLPE-Insulated-Armoured-PVC-Sheathed-Power-Cable (1)foreign customers in our factory


copper wire screen procedure

Package

package group1


Payment and delivery

PaymentShipping Method


Honor

Certificates

Looking for ideal Overhead Cable for Transmission Lines Manufacturer & supplier ? We have a wide selection at great prices to help you get creative. All the ACAR Overhead Conductors Cable are quality guaranteed. We are China Origin Factory of Aluminum Alloy Conductors Cores Cable. If you have any question, please feel free to contact us.

Product Categories : Overhead Cable

Email to this supplier
  • *Subject:
  • *Messages:
    Your message must be between 20-8000 characters
Communicate with Supplier?Supplier
Crazy Zhang Mr. Crazy Zhang
What can I do for you?
Chat Now Contact Supplier