Huayuan Gaoke Cable Co.,Ltd.
Overhead Cable for Transmission Lines,ACAR Overhead Conductors Cable,Aluminum Alloy Conductors Cores Cable
Payment Type: | L/C,T/T,D/P,Paypal,Money Gram,Western Union |
---|---|
Incoterm: | FOB,CFR,CIF,FCA,CPT,CIP |
Min. Order: | 1000 Meter |
Model No.: ACAR
Brand: HUAYUAN YONGTONG
Brand: HUAYUAN YONGTONG
Packaging: Drum
Productivity: 1000km/M
Transportation: Ocean,Land,Air
Place of Origin: Beijing,China
Supply Ability: 1000km/M
Certificate: CE,CCC,ISO
Port: Tianjin Port,Shanghai Port,Qingdao Port
Payment Type: L/C,T/T,D/P,Paypal,Money Gram,Western Union
Incoterm: FOB,CFR,CIF,FCA,CPT,CIP
1) CSC-NPA-LT-NPAPA- HCTEM-0001
2) CSC-NPA-LT-NPACON- HCTEM-0001
3) CSC-NPA-LT-NPAPAR- HCTEM-0001
ITÉM | FEATURES | UNIT | REQUESTED | GUARANTEED |
1 | MANUFACTURER | |||
1.1 | Name | - | indicate | Beijing Huayuan |
1.2 | Country | - | indicate | CHINA |
2 | COMPLETE CONDUCTOR FEATURES | |||
2.1 | Conductor type | - | ACAR | ACAR |
2.2 | Standards that fulfill | - | ASTM B-524 | ASTM B-524 |
2.3 | Nominal Cross section | mm2 | 380 | 380 |
2.4 | Nominal external diameter | mm | 25.31 | 25.31 |
2.5 | Nominal unit weight | kg/km | 1047 | 1049 |
2.6 | Minimum breaking strength | kg | 7056 | 7056 |
2.7 | Number of wires | each | 30/7 | 30/7 |
2.8 | Elasticity module | |||
· Initial | kg/mm2 | indicate | 5700 | |
· Final | kg/mm2 | indicate | 5700 | |
2.9 | Linear expansion Coefficient | 1/°C | 23 x 10-6 | 23 x 10-6 |
2.1 | A.C. Electrical resistance , 50 hz ,at 25 °C | Ω/km | indicate | ≤0.09795 |
2.11 | Coefficient of variation of electrical resistance with temperature. | 1/°C | indicate | 0.00403 |
2.12 | Reactance at 1 foot and 50 Hz |
|
|
|
· Inductive | Ω/km | indicate | 0.233 | |
· Capacitive | Ω/km | indicate | / | |
2.13 | Geometric Mean Radius | mm | indicate | / |
3 | ALUMINUM ALLOY WIRES | |||
3.1 | Standards that fulfill | - | ASTM B-398 | ASTM B-398 |
3.2 | Nominal diameter | mm | 3.62 | 3.62 |
3.3 | Minimum Conductivity at 20°C, 50 Hz | % IACS | indicate | 53.5 |
3.4 | Minimum average breaking strength | |||
· before wiring | MPa | indicate | 315 | |
· after wiring | MPa | indicate | 302 | |
3.5 | Minimum average elongation at 254 mm | |||
· before wiring | % | indicate | 3 | |
· after wiring | % | indicate | 2 | |
3.6 | Type of welding and welding wire treatment | - | indicate | cold welding |
3.7 | Minimum tensile strength on welded wire | MPa | indicate | 302 |
3.8 | Elasticity module | MPa | indicate | 56000 |
3.9 | Linear expansion Coefficient | 1/°C | 23 x 10-6 | 23 x 10-6 |
3.1 | Chemical composition | |||
· Aluminum, mínimum | % Peso | indicate | 97.28 | |
· Copper, máximum | % Peso | indicate | 0.1 | |
· iron , máximum | % Peso | indicate | 0.5 | |
· Silicon , range | % Peso | indicate | 0.50-0.9 | |
· Manganese, máximum | % Peso | indicate | 0.03 | |
· Magnesium, máximum range | % Peso | indicate | 0.6-0.9 | |
· Zinc, máximum | % Peso | indicate | 0.10 | |
· Chromo, máximum | % Peso | indicate | 0.03 | |
· Boron, máximum | % Peso | indicate | 0.06 | |
· Others elements, máximum | % Peso | indicate | 0.10 | |
4 | REELS | |||
4.1 | Nominal length of the continuous cable strip | m | 2000 | 2000 |
4.2 | Reel gross weight , including OPGW cable and lathing | kg | indicate | 2298(including ACAR ) |
4.3 | External diameter over lathing | cm | indicate | 180 |
4.4 | Flange diameter | cm | indicate | 180 |
4.5 | Drum diameter | cm | indicate | 180 |
4.6 | Inside width , between flanges | cm | indicate | 940 |
4.7 | External width | cm | indicate | 1100 |
4.8 | Hole diameter for axis | cm | indicate | 160 |
4.9 | Number of bolts of flanges | - | indicate | 8 |
4.1 | Material from which the reel is made | - | indicate | TBEA |
5 | QUANTITIES | |||
5.1 | ACAR CONDUCTOR | km | 1830 | 1830 |
6 | TESTS | |||
6.1 | Test list | - | indicate | YES |
6.2 | Test Protocols | - | indicate | YES |
6.3 | Period of tests in factory | - | indicate | YES |
7 | DELIVERY TIME | |||
7.1 | Delivery date certified information | - | indicate |
|
7.2 | Delivery term | - | indicate |
|
7.3 | Certified information, catalogs, plans, etc. | - | indicate |
|
7.4 | Gantt chart | - | indicate |
|
Conductor Structure for ACAR 750 MCM
Construction | Nominal NO./Diameter(mm) | Nominal Diameter(mm) |
1--- Aluminum Alloy Wire | 7 / 3.62 | 10.86 |
2--- Aluminum Wire | 30 / 3.62 | 25.34 |
Test Requirements for Overhead Conductor
The following test items shall be carried out in accordance with relevant ASTM standards.
No. | Test item |
Tests(The user has no special requirements) | |
1 | Tensile Strength and Elongation Requirements (test frequency 10%)Before strands |
2 | Resistivity test(test frequency 10%) |
3 | Structural inspection(test frequency 10%) |
Package
Payment and delivery
Honor